Models : PFT
Features :
MECO AC Power Factor Transducers measure the power Factor in 1 Phase and 3 Phase electrical systems. The resulting output signal is directly proportional to the system power factor. These Transducers provide an output which is load independent and isolated from the input. The output can be connected to Controllers, Data-Loggers, PLC's Analog/Digital Indicators, Recorders for display, analysis or control. They are ideal for SCADA, Energy Management, Telemetering for Remote, Local as well as Central Monitoring System.
Type
DIN Series
Standards
IEC 688 / EN 60688, EN 61010-1, EN 61326-1, IS12784 (Part-1) 1989
AC Input
- Voltage : 63.5 / 110 / 230 / 440V (any one only)
- Current : 1A / 5A (any one only)
- Frequency : 50 / 60 Hz (any one only)
- P.F.Range : 0.5 (Lag) - 1.0 - 0.5 (Lead) / 0.8 (Lag) - 1.0 - 0.2 (Lead)
DC Output
- Current : 0-1, 0-5, 0-10, 2-10, 0-20, 4-20mA
- Voltage : 0-1, 0-5, 1-5, 0-10, 2-10V
Accuracy
- Standard : ± 0.5% of Span
Auxiliary
- 110/230V AC ± 20%
- 24/48/110/220V DC ± 20%
- Self powered Available. Refer PDF
Isolation
Complete (Input / Output / Auxiliary / Case)
Dielectric Strength
- Strength 2.5kV at 50Hz for 1 min. (Standard)
- 4kV(Optional), across
- Casing - Input / Output / Auxiliary
- Input - Output
- Input - Auxiliary
- Output - Auxiliary