Detail RING TYPE CURRENT TRANsFORMERS - ORX S
Current Transformer
Technical data
Highest voltage for equipment 0.72 kV
Power-frequency withstand voltage 3 kV
Rated primary current Ipn 50 to 4000 A
Rated secondary current Isn 5 or 1 A
Rated frequency 50 Hz or 60 Hz
Network nominal voltage 0.75 - 20 - 72.5 - 100 - 245 - ... - 1000kV
Rated output Up to 500 VA
Accuracy class 0.2 - 0.2S - 0.5 - 0.5S - 1 - 5P - 10P
Accuracy limit factor 5 - 10 - 15 - 20 - 30
Continuous thermal current 1.2 Ipn
Short-time thermal current 80 Ipn
Dynamic current Idyn 2.5 Ith
Inner diameter 53 to 250 mm
Ambient temperature -25°C to + 40°C
Insulation material Cast resin
Insulation class E
Base plate or fixing brackets U-shape brackets - galvanized steel
Standards IEC - IEEE - CSA - AS - BS
Other characteristics on request
Highest voltage for equipment 2 kV
Power-frequency withstand voltage 6 kV
Multi-ratio by secondary tapping
Accuracy class PX, PXR, PR, TPS, TPX, TPY, TPZ
Ambient temperature - 40°C to + 70°C
Temukan produk-produk serupa lainnya pada website kami!
Hubungi kami pada kontak yang tertera dibawah ini untuk pemesanan atau informasi lebih lanjut.
ANEKA DAYA INDONESIA
Jalan Matematika IV No 43 Kel Jatikramat Kec Jatiasih, Bekasi Jawa Barat
Telepon: 02185508158
Tampilkan Lebih Banyak